Will my radiators work with a heat pump in Sherman?

Almost certainly not at the size they are. A radiator gives its catalogue output at 75/65 into a 20 °C room; a heat pump runs far cooler, and output falls faster than the temperature does. Against Sherman’s design temperature of −6.3 °C, here is what that costs.

Design temperature −6.3 °C
55/45 51%
45/35 30%

What a radiator delivers at each flow temperature

Share of the catalogue rating, and the catalogue rating a room would need to stay warm. EN 442 rates radiators at 75/65 into a 20 °C room.

Flow / return Mean ΔT Output Rating needed per kW of demand
75/65 50 K 100% 1.00 kW
65/55 40 K 75% 1.34 kW
55/45 30 K 51% 1.94 kW
50/40 25 K 41% 2.46 kW
45/35 20 K 30% 3.29 kW
40/30 15 K 21% 4.78 kW
35/30 13 K 16% 6.06 kW

What that means room by room

Heat demand for a room in this climate, and the catalogue radiator rating needed to meet it at each flow temperature. For an insulated 1980s house; change the construction in the calculator.

Room W 65/55 55/45 50/40 45/35 40/30 35/30
Living room 1,178 1,575 2,289 2,901 3,878 5,637 7,144
Bedroom 687 919 1,335 1,693 2,262 3,288 4,167
Kitchen 589 787 1,145 1,451 1,939 2,818 3,572
Bathroom 295 394 572 725 969 1,409 1,786

Check the radiator on your wall

Take the output printed on the radiator or in its datasheet — it will be quoted at ΔT50 — and the floor area of the room it heats.

Verdict

Why output falls so fast

Radiator output follows Q = Q₅₀ × (ΔT/50)^1.3, where ΔT is the mean water temperature minus the room temperature. The exponent is what does the damage: halving the temperature difference does not halve the output, it cuts it to about 40 per cent.