heatload

Heating load in Barrow in Furness

A home in Barrow in Furness has to be heated against a design temperature of −2.5 °C. That figure is measured, not modelled: it is the 1st percentile of daily minimum temperature over 29 years at Walney Island, 3 km away.

Design temperature −2.5 °C
Heating degree days 2,053
Coldest month Jan
Coldest night on record −7.0 °C
Coldest station in range −4.0 °C

How many kilowatts

Heating power needed at the design temperature, in kilowatts, for a detached house. Pick the row that matches the building.

Construction Detached Semi-detached Terraced Top-floor flat Mid-floor flat Ground-floor flat
Uninsulated, single glazed 14.5 kW 12.7 kW 11.3 kW 12.4 kW 6.0 kW 7.4 kW
Unfilled cavity, early double glazing 9.8 kW 8.5 kW 7.4 kW 7.2 kW 4.4 kW 5.5 kW
Insulated to 1980s standards 5.6 kW 5.0 kW 4.6 kW 4.3 kW 3.1 kW 4.0 kW
Modern, roughly 1995-2010 3.5 kW 3.1 kW 2.9 kW 2.8 kW 2.1 kW 2.5 kW
Current building regulations 2.6 kW 2.4 kW 2.2 kW 2.2 kW 1.6 kW 2.0 kW
Passive house 1.6 kW 1.4 kW 1.3 kW 1.2 kW 0.8 kW 1.1 kW

Where the heat goes

For a 120 m2 detached house of this construction, at the design temperature.

Element W Share
Walls 1,848 33%
Roof 540 10%
Ground floor 365 7%
Windows 1,053 19%
Thermal bridges 309 6%
Ventilation and draughts 1,492 27%
Heating load 5,607 5.6 kW

Calculate it for your own home

The climate half of this is measured. The building half is yours to supply.

Heating load

Monthly mean temperature

JanFebMarAprMayJunJulAugSepOctNovDec
°C 5.2 5.2 6.4 8.6 11.5 13.9 15.8 15.8 14.0 11.1 8.1 5.8

Where these numbers come from