Heating load in Ballymena

A home in Ballymena has to be heated against a design temperature of −3.3 °C. That figure is measured, not modelled: it is the 1st percentile of daily minimum temperature over 26 years at Portglenone, 11 km away.

Design temperature −3.3 °C
Heating degree days 2,298
Coldest month Jan
Coldest night on record −13.4 °C
Coldest station in range −6.0 °C

How many kilowatts

Heating power needed at the design temperature, in kilowatts, for a detached house. Pick the row that matches the building.

Construction Detached Semi-detached Terraced Top-floor flat Mid-floor flat Ground-floor flat
Uninsulated, single glazed 15.0 kW 13.2 kW 11.7 kW 12.8 kW 6.3 kW 7.6 kW
Unfilled cavity, early double glazing 10.2 kW 8.8 kW 7.6 kW 7.4 kW 4.5 kW 5.7 kW
Insulated to 1980s standards 5.8 kW 5.2 kW 4.8 kW 4.5 kW 3.2 kW 4.1 kW
Modern, roughly 1995-2010 3.6 kW 3.3 kW 3.0 kW 2.9 kW 2.2 kW 2.6 kW
Current building regulations 2.7 kW 2.5 kW 2.3 kW 2.2 kW 1.7 kW 2.1 kW
Passive house 1.6 kW 1.5 kW 1.3 kW 1.3 kW 0.9 kW 1.1 kW

Where the heat goes

For a 120 m2 detached house of this construction, at the design temperature.

Element W Share
Walls 1,914 33%
Roof 559 10%
Ground floor 377 7%
Windows 1,090 19%
Thermal bridges 320 6%
Ventilation and draughts 1,545 27%
Heating load 5,806 5.8 kW

Calculate it for your own home

The climate half of this is measured. The building half is yours to supply.

Heating load

Monthly mean temperature

JanFebMarAprMayJunJulAugSepOctNovDec
°C 4.8 4.9 6.0 8.1 10.6 13.0 14.6 14.5 12.7 10.0 7.1 5.0

Where these numbers come from