Heating load in Prince Edward

A home in Prince Edward has to be heated against a design temperature of −22.2 °C. That figure is measured, not modelled: it is the 1st percentile of daily minimum temperature over 28 years at Point Petre (Aut) Ont, 20 km away.

Design temperature −22.2 °C
Heating degree days 3,291
Coldest month Jan
Coldest night on record −31.7 °C
Coldest station in range −23.7 °C

How many kilowatts

Heating power needed at the design temperature, in kilowatts, for a detached house. Pick the row that matches the building.

Construction Detached Semi-detached Terraced Top-floor flat Mid-floor flat Ground-floor flat
Uninsulated, single glazed 27.2 kW 23.9 kW 21.2 kW 23.2 kW 11.3 kW 13.9 kW
Unfilled cavity, early double glazing 18.4 kW 15.9 kW 13.9 kW 13.5 kW 8.2 kW 10.2 kW
Insulated to 1980s standards 10.5 kW 9.5 kW 8.6 kW 8.1 kW 5.8 kW 7.4 kW
Modern, roughly 1995-2010 6.5 kW 5.9 kW 5.4 kW 5.2 kW 3.9 kW 4.8 kW
Current building regulations 5.0 kW 4.5 kW 4.2 kW 4.1 kW 3.1 kW 3.7 kW
Passive house 2.9 kW 2.6 kW 2.4 kW 2.3 kW 1.6 kW 2.1 kW

Where the heat goes

For a 120 m2 detached house of this construction, at the design temperature.

Element W Share
Walls 3,467 33%
Roof 1,013 10%
Ground floor 684 7%
Windows 1,975 19%
Thermal bridges 580 6%
Ventilation and draughts 2,798 27%
Heating load 10,516 10.5 kW

Calculate it for your own home

The climate half of this is measured. The building half is yours to supply.

Heating load

Monthly mean temperature

JanFebMarAprMayJunJulAugSepOctNovDec
°C −5.0 −4.2 −0.4 4.9 10.5 15.8 20.3 20.8 17.2 10.9 5.0 −1.0